Filtered and prioritized hazard inventory across all workstations and facilities.
| Risk / Score | Location / Station | Category | Hazard Description | Sev | Lik | Score | Control Measures | Action |
|---|---|---|---|---|---|---|---|---|
| High (50) |
FR1
Medium Voltage
Transformer Hi Pot
|
Electric Shock or Arc Flash | Electric shock | 10 | 5 | 50 |
1. Surround the transformer with touch-safe barrier 2. Wear PPE per NFPA Shock and Arc Flash label |
JHA #26 |
| High (40) |
Waukegan
Field Service - PhotoVoltaic
Field Service
|
Electric Shock or Arc Flash | Electric Shock / Arc Flash | 10 | 4 | 40 | Verify the customer locked out all upstream power supply devices. Refer to one-line drawing to ensure this was done. While wearing appropriate PPE and using voltage rated equipment, verify absence of power | JHA #28 |
| High (40) |
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
|
Electric Shock or Arc Flash | Electric shock or arc flash | 10 | 4 | 40 |
Door interlocks prevent doors to be opened if medium voltage is present. Follow PPE requirements on NFPA label, or NFPA 70E tables if incident energy study has not yet been performed. |
JHA #27 |
| Moderate (30) |
FR1
LV Test
Test 3
|
Electric Shock or Arc Flash | Electric shock from contact with exposed voltage | 10 | 3 | 30 |
1. Process performed by trained testers who are certified in NFPA 70E requirements 2. Electrical PPE 3. Fast acting short circuit protection reduces potential severity |
JHA #33 |
| Moderate (30) |
FR1
LV Test
Test 3
|
Electric Shock or Arc Flash | Arc flash inside the variable frequency drive if the wrong voltage is applied | 6 | 5 | 30 |
1. All of the previous steps are designed to prevent an arc flash within the variable frequency drive 2. The drive cover is installed and will contain the arc flash and blast 3. The tester is at the test stand and not standing over or directly in front of the drive. This places the person outside of the arc flash boundary. 4. Fast acting short circuit protection immediately removes power to the drive to control the blast |
JHA #33 |
| Moderate (30) |
FR1
LV Test
Test 3
|
Electric Shock or Arc Flash | Incorrect installation can cause arc flash hazard at subsequent step | 6 | 5 | 30 |
1. Color coded phase wire leads 2. Installation by trained, competent assocaite |
JHA #33 |
| Moderate (30) |
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
|
Electric Shock or Arc Flash | Arc Flash during re-energization | 10 | 3 | 30 | Power turned on at upstream device following left hand rule. | JHA #27 |
| Moderate (25) |
FR1
LV Test
Test 3
|
Electric Shock or Arc Flash | While there is no electrical hazard at this time, failure to correctly select the voltage can cause in arc flash inside the drive at a subsequent step | 5 | 5 | 25 |
1. Multiple step voltage verification by trained, competent associate 2. Drive cover contains the arc blast energy 3. Fast acting short circuit protection |
JHA #33 |
| Moderate (20) |
FR1
Floor Mount Line
Panel Wiring
|
Cut by/Punctured by | Cut or pinch by blades or jaws | 5 | 4 | 20 | Guard on power crimpers. Ensure hands are clear of cutter blades and crimper jaws | JHA #32 |
| Moderate (20) |
FR1
Medium Voltage
Transformer Hi Pot
|
Electric Shock or Arc Flash | Arc flash | 10 | 2 | 20 |
1. Surround the transformer with touch-safe barrier 2. Wear PPE per NFPA Shock and Arc Flash label |
JHA #26 |
| Moderate (18) |
FR1
LV Test
Test 3
|
Electric Shock or Arc Flash | Arc flash at other components if the test leads are installed incorrectly, there is miswiring or loose power connections in the unit, or incorrect components installed | 6 | 3 | 18 |
1. Administrative controls taken at previous steps, including multiple checks prior to this job, are designed to protect against this failure. 2. The tester is at the test stand and not standing over or directly in front of the drive. This places the person outside of the arc flash boundary. 3. Fast acting short circuit protection immediately removes power to the drive to control the blast |
JHA #33 |
| Moderate (18) |
FR1
Floor Mount Line
Panel Wiring
|
Struck-by, Struck-against | Wire cutting and stripping can send cut wire ends airborne striking the eyes | 6 | 3 | 18 | Safety glasses with side shields | JHA #32 |
| Moderate (16) |
FR1
Floor Mount Line
Panel Wiring
|
Ergonomics/Over-Exertion | Squeezing tool too hard with wrong body mechanics can place strain on soft tissue | 4 | 4 | 16 | Hold tool with enough pressure to maintain control but without excess tension in hands. Perform reverse stretching every 20-minutes if frequent torquing is required | JHA #32 |
| Moderate (16) |
FR1
MV Assembly
Frame 1 A Frame
|
Struck-by, Struck-against | struck by power cell | 8 | 2 | 16 | 0 | JHA #25 |
| Low (10) |
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
|
Other | Environmental hazards to be assessed on site. | 5 | 2 | 10 |
Customer to present environmental and local hazards with controls. Yaskawa engineer to assess if customer controls are sufficient (If customer control is higher than Yaskawa requirements, associate shall follow customer controls. If Yaskawa controls are greater than customer, the associate shall follow Yaskawa controls). Walk around work site to identify hazards and determine proper controls. |
JHA #27 |
| Low (10) |
FR1
Floor Mount
Panel Prep and Assembly
|
Struck-by, Struck-against | improperly secured load could fall | 5 | 2 | 10 | 0 | JHA #24 |
| Low (9) |
FR1
LV Test
Test 3
|
Electric Shock or Arc Flash | No hazard at this step but failure to perform this step can lead to damaged parts at subsequent steps | 3 | 3 | 9 | 1. Correct components are checked three times: upon pulling for the order, upon installation, and at test | JHA #33 |
| Low (9) |
FR1
LV Test
Test 3
|
Electric Shock or Arc Flash | No hazard at this step but failure to perform this step can lead to damaged parts at subsequent steps | 3 | 3 | 9 |
1. Correct components are checked three times: upon pulling for the order, upon installation, and at test 2. Competent tester performing continuity check reduces the chance of arc flash and quality defects at power-on step |
JHA #33 |
| Low (9) |
Waukegan
Field Service - PhotoVoltaic
Field Service
|
Other | PV sites can have multiple hazards including trip, animal/insects, electrical, construction activity | 3 | 3 | 9 | Inspect site for hazards and determine required controls. | JHA #28 |
| Low (8) |
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
|
Other | Internal component failure, Unexpected motor rotation | 4 | 2 | 8 | Slow start-up | JHA #27 |
| Low (6) |
FR1
Floor Mount Line
Panel Wiring
|
Struck-by, Struck-against | Conveyor pushed off conveyor | 2 | 3 | 6 | Verify conveyor being transferred to has gates up to prevent it from rolling off the edge | JHA #32 |
| Low (6) |
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
|
Struck-by, Struck-against | Working in tight area increases risk of striking a body part against a fixed object | 2 | 3 | 6 | Inspect the work area and plan movements | JHA #27 |
| Low (4) |
FR1
Floor Mount Line
Panel Wiring
|
Caught-in/Caught In-between | Fingers pinched between conveyor roller and panel | 2 | 2 | 4 | Move panel by holding on top of panel, not the edges. Manual conveyor so control remains with operator. | JHA #32 |
| Low (4) |
FR1
O&G Assembly
Panel Integration
|
Struck-by, Struck-against | Pinch point and Fall Hazard | 4 | 1 | 4 | Engineering Control | JHA #31 |
| Low (0) |
FR1
O&G Assembly
Panel Integration
|
Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 252 |
Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 256 |
0 | 0 | 0 |
Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 268 |
JHA #30 |
| Low (0) |
FR1