Master Hazard Register

Filtered and prioritized hazard inventory across all workstations and facilities.

Dashboard
Filter Hazards
Reset
Hazards List (Showing 26 records) Sorted by: Score (DESC)
Risk / Score Location / Station Category Hazard Description Sev Lik Score Control Measures Action
High (50)
FR1
Medium Voltage
Transformer Hi Pot
Electric Shock or Arc Flash Electric shock 10 5 50 1. Surround the transformer with touch-safe barrier
2. Wear PPE per NFPA Shock and Arc Flash label
JHA #26
High (40)
Waukegan
Field Service - PhotoVoltaic
Field Service
Electric Shock or Arc Flash Electric Shock / Arc Flash 10 4 40 Verify the customer locked out all upstream power supply devices. Refer to one-line drawing to ensure this was done. While wearing appropriate PPE and using voltage rated equipment, verify absence of power JHA #28
High (40)
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
Electric Shock or Arc Flash Electric shock or arc flash 10 4 40 Door interlocks prevent doors to be opened if medium voltage is present.

Follow PPE requirements on NFPA label, or NFPA 70E tables if incident energy study has not yet been performed.
JHA #27
Moderate (30)
FR1
LV Test
Test 3
Electric Shock or Arc Flash Electric shock from contact with exposed voltage 10 3 30 1. Process performed by trained testers who are certified in NFPA 70E requirements
2. Electrical PPE
3. Fast acting short circuit protection reduces potential severity
JHA #33
Moderate (30)
FR1
LV Test
Test 3
Electric Shock or Arc Flash Arc flash inside the variable frequency drive if the wrong voltage is applied 6 5 30 1. All of the previous steps are designed to prevent an arc flash within the variable frequency drive
2. The drive cover is installed and will contain the arc flash and blast
3. The tester is at the test stand and not standing over or directly in front of the drive. This places the person outside of the arc flash boundary.
4. Fast acting short circuit protection immediately removes power to the drive to control the blast
JHA #33
Moderate (30)
FR1
LV Test
Test 3
Electric Shock or Arc Flash Incorrect installation can cause arc flash hazard at subsequent step 6 5 30 1. Color coded phase wire leads
2. Installation by trained, competent assocaite
JHA #33
Moderate (30)
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
Electric Shock or Arc Flash Arc Flash during re-energization 10 3 30 Power turned on at upstream device following left hand rule. JHA #27
Moderate (25)
FR1
LV Test
Test 3
Electric Shock or Arc Flash While there is no electrical hazard at this time, failure to correctly select the voltage can cause in arc flash inside the drive at a subsequent step 5 5 25 1. Multiple step voltage verification by trained, competent associate
2. Drive cover contains the arc blast energy
3. Fast acting short circuit protection
JHA #33
Moderate (20)
FR1
Floor Mount Line
Panel Wiring
Cut by/Punctured by Cut or pinch by blades or jaws 5 4 20 Guard on power crimpers. Ensure hands are clear of cutter blades and crimper jaws JHA #32
Moderate (20)
FR1
Medium Voltage
Transformer Hi Pot
Electric Shock or Arc Flash Arc flash 10 2 20 1. Surround the transformer with touch-safe barrier
2. Wear PPE per NFPA Shock and Arc Flash label
JHA #26
Moderate (18)
FR1
LV Test
Test 3
Electric Shock or Arc Flash Arc flash at other components if the test leads are installed incorrectly, there is miswiring or loose power connections in the unit, or incorrect components installed 6 3 18 1. Administrative controls taken at previous steps, including multiple checks prior to this job, are designed to protect against this failure.
2. The tester is at the test stand and not standing over or directly in front of the drive. This places the person outside of the arc flash boundary.
3. Fast acting short circuit protection immediately removes power to the drive to control the blast
JHA #33
Moderate (18)
FR1
Floor Mount Line
Panel Wiring
Struck-by, Struck-against Wire cutting and stripping can send cut wire ends airborne striking the eyes 6 3 18 Safety glasses with side shields JHA #32
Moderate (16)
FR1
Floor Mount Line
Panel Wiring
Ergonomics/Over-Exertion Squeezing tool too hard with wrong body mechanics can place strain on soft tissue 4 4 16 Hold tool with enough pressure to maintain control but without excess tension in hands. Perform reverse stretching every 20-minutes if frequent torquing is required JHA #32
Moderate (16)
FR1
MV Assembly
Frame 1 A Frame
Struck-by, Struck-against struck by power cell 8 2 16 0 JHA #25
Low (10)
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
Other Environmental hazards to be assessed on site. 5 2 10 Customer to present environmental and local hazards with controls. Yaskawa engineer to assess if customer controls are sufficient (If customer control is higher than Yaskawa requirements, associate shall follow customer controls. If Yaskawa controls are greater than customer, the associate shall follow Yaskawa controls).

Walk around work site to identify hazards and determine proper controls.
JHA #27
Low (10)
FR1
Floor Mount
Panel Prep and Assembly
Struck-by, Struck-against improperly secured load could fall 5 2 10 0 JHA #24
Low (9)
FR1
LV Test
Test 3
Electric Shock or Arc Flash No hazard at this step but failure to perform this step can lead to damaged parts at subsequent steps 3 3 9 1. Correct components are checked three times: upon pulling for the order, upon installation, and at test JHA #33
Low (9)
FR1
LV Test
Test 3
Electric Shock or Arc Flash No hazard at this step but failure to perform this step can lead to damaged parts at subsequent steps 3 3 9 1. Correct components are checked three times: upon pulling for the order, upon installation, and at test
2. Competent tester performing continuity check reduces the chance of arc flash and quality defects at power-on step
JHA #33
Low (9)
Waukegan
Field Service - PhotoVoltaic
Field Service
Other PV sites can have multiple hazards including trip, animal/insects, electrical, construction activity 3 3 9 Inspect site for hazards and determine required controls. JHA #28
Low (8)
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
Other Internal component failure, Unexpected motor rotation 4 2 8 Slow start-up JHA #27
Low (6)
FR1
Floor Mount Line
Panel Wiring
Struck-by, Struck-against Conveyor pushed off conveyor 2 3 6 Verify conveyor being transferred to has gates up to prevent it from rolling off the edge JHA #32
Low (6)
Waukegan
Field Service - Medium Voltage Commissioning
Customer Site
Struck-by, Struck-against Working in tight area increases risk of striking a body part against a fixed object 2 3 6 Inspect the work area and plan movements JHA #27
Low (4)
FR1
Floor Mount Line
Panel Wiring
Caught-in/Caught In-between Fingers pinched between conveyor roller and panel 2 2 4 Move panel by holding on top of panel, not the edges. Manual conveyor so control remains with operator. JHA #32
Low (4)
FR1
O&G Assembly
Panel Integration
Struck-by, Struck-against Pinch point and Fall Hazard 4 1 4 Engineering Control JHA #31
Low (0)
FR1
O&G Assembly
Panel Integration

Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 252

Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 256
0 0 0
Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 268
JHA #30
Low (0)
FR1
O&G Assembly
Panel Integration

Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 252

Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 256
0 0 0
Deprecated: htmlspecialchars(): Passing null to parameter #1 ($string) of type string is deprecated in /homepages/8/d663429354/htdocs/JHA/view_hazards.php on line 268
JHA #29