Job Hazard Analysis (JHA) #33

JHA Header Information

Identified Hazards & Required Controls (Most Critical First)[cite: 7]
Task 1: Verify voltage

1. Verify the voltage on the drive cover, production order, and shipping label are all the same.
2. Set the Motor VAC to match the voltage of the drive identified in Step 1.
3. Set the "SOURCE VAC" to "VARIAC" for 200 Volt drives and set to "LINE" for 480 Volt Drives. Set to "VARIAC" for 600 Volt Drives at 600 Volt test Stands
4. Place a magnet or indicator to indicate the voltage has been selected. If tester has to leave the station, return voltages to OFF and start over at step 1 upon return

Energy / Category Hazard Description Risk Level Mandatory Control Measures
Electric Shock or Arc Flash While there is no electrical hazard at this time, failure to correctly select the voltage can cause in arc flash inside the drive at a subsequent step Moderate (Score: 25) 1. Multiple step voltage verification by trained, competent associate
2. Drive cover contains the arc blast energy
3. Fast acting short circuit protection
Task 2: Verify Correct Components

Verify the critical electromechanical components match the description in the production order

Energy / Category Hazard Description Risk Level Mandatory Control Measures
Electric Shock or Arc Flash No hazard at this step but failure to perform this step can lead to damaged parts at subsequent steps Low (Score: 9) 1. Correct components are checked three times: upon pulling for the order, upon installation, and at test
Task 3: Pre-Power Verifications

1. Verify the critical electromechanical components match the description in the production order
2. For Bypass units, connect communication cable to bypass board to capture serial number
3. Perform continuity check to ensure correct wiring

Energy / Category Hazard Description Risk Level Mandatory Control Measures
Electric Shock or Arc Flash No hazard at this step but failure to perform this step can lead to damaged parts at subsequent steps Low (Score: 9) 1. Correct components are checked three times: upon pulling for the order, upon installation, and at test
2. Competent tester performing continuity check reduces the chance of arc flash and quality defects at power-on step
Task 4: Add Power Cables to Unit Under Test (UUT)

1. Connect AC input cables to UUT input component (e.g., Circuit Breaker, Disconnect, directly to drive on some configured units)
2. Connect motor output wires
3. On Bypass units, install Safety Circuit Jumpers

Energy / Category Hazard Description Risk Level Mandatory Control Measures
Electric Shock or Arc Flash Incorrect installation can cause arc flash hazard at subsequent step Moderate (Score: 30) 1. Color coded phase wire leads
2. Installation by trained, competent assocaite
Task 5: Apply Power to Unit Under Test (UUT)

1. Don required PPE (ear plugs required when applying power, electrical gloves with leather protectors, long sleeve all natural fiber shirt - Safety Glasses and Electrical Hazard shoes are required for all steps in this process)
2. Using the Left Hand Rule, turn the Test Stand Disconnect to the On position.

Energy / Category Hazard Description Risk Level Mandatory Control Measures
Electric Shock or Arc Flash Arc flash inside the variable frequency drive if the wrong voltage is applied Moderate (Score: 30) 1. All of the previous steps are designed to prevent an arc flash within the variable frequency drive
2. The drive cover is installed and will contain the arc flash and blast
3. The tester is at the test stand and not standing over or directly in front of the drive. This places the person outside of the arc flash boundary.
4. Fast acting short circuit protection immediately removes power to the drive to control the blast
Electric Shock or Arc Flash Arc flash at other components if the test leads are installed incorrectly, there is miswiring or loose power connections in the unit, or incorrect components installed Moderate (Score: 18) 1. Administrative controls taken at previous steps, including multiple checks prior to this job, are designed to protect against this failure.
2. The tester is at the test stand and not standing over or directly in front of the drive. This places the person outside of the arc flash boundary.
3. Fast acting short circuit protection immediately removes power to the drive to control the blast
Task 6: Power On Test

1. Check voltage going into the drive at the disconnect and at the drive input
• If the correct voltage is at the disconnect but incorrect at the drive, check voltages at each component in line to troubleshoot
2. Perform Factory Reset on the Drive
3. Check fan air flow is in the correct direction
4. Set thermostat
5. Connect cable to bypass board (Bypass units only) to perform Load Bank Test
6. Turn Test Stand Disconnect to Off Position
7. Reset Drive and Power Power Switches on test stand to Zero or Off position

Energy / Category Hazard Description Risk Level Mandatory Control Measures
Electric Shock or Arc Flash Electric shock from contact with exposed voltage Moderate (Score: 30) 1. Process performed by trained testers who are certified in NFPA 70E requirements
2. Electrical PPE
3. Fast acting short circuit protection reduces potential severity

Station Details

Station Controls

Signs Barriers Other Controls

Environmental Factors

Workstation Images

Required Competencies

Tools Used

Chemicals Used

Job Tasks and Hazards

Required PPE

Eye Protection
Safety Glasses w/ Shields
Vented Goggles
Non-Vented Goggles
Welding Helmet/Shield
Laser Protection
UV Protection
Face Shield
Head Protection
Type 2 Class G
Bump Cap
Hearing Protection
Hearing Protection
Respiratory Protection
Filtered Face Mask
Half-Face P100
Organic Vapor
Foot Protection
Toe Protection
Electrical Hazard
ESD
Metatarsal
Puncture Resistant
Chemical Resistant
Electrical Protection
Class 0 Gloves
Class 1 Gloves
Class 2 Gloves
CAT 1 Arc
CAT 2 Arc
CAT 3 Arc
CAT 4 Arc
Natural Fiber
Arc-Rated Clothes

Ergonomic Assessment

Wrists
PosturesForceDurationFrequency
Left Wrist
Right Wrist
Ergonomic Stressors